LL-114/T3, LL-214/T3, LL-221/T3, LL-133/T3, LL-233/T3, LL-243/T3
IMPA Code:33 19 01 - LL-133/T3, 33 19 02 - LL-233/T3
The Wolf ATEX transformers have a CE mark and are safe to use in places with explosive gases (Zone 1) and dust (Zone 21). They can be used where certain temperatures are allowed. These transformers are certified by both ATEX and IECEx for safety.
For Output Power ≤ 400VA
II2 GD Ex d e IIC T3 Gb
Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +35°C)
For Output Power ≤ 320VA
II2 GD Ex d e IIC T3 Gb
Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +50°C)
For Output Power ≤ 400VA
II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +30°C)
For Output Power ≤ 320VA
II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +42°C)
ATEX 400VA Transformer |
||||||
PRODUCT REFERENCE |
LL-114/T3 |
LL-214/T3 |
LL-221/T3 |
LL-133/T3 |
LL-233/T3 |
LL-243/T3 |
PRODUCT DESCRIPTION |
GRP |
Stainless Steel |
||||
110V:24V |
230V:24V |
230V:110V |
110V:24V |
230V:24V |
230V:110V |
|
CODE |
For Output Power ≤ 400VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +35°C) For Output Power ≤ 320VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +50°C) |
For Output Power ≤ 400VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +30°C) For Output Power ≤ 320VA II2 GD Ex d e IIC T3 Gb Ex t IIIC T195°C Db IP66 (-20°C ≤ Ta ≤ +42°C) |
||||
TYPE OF PROTECTION |
'e' increased safety, 'd' flameproof |
|||||
AREA OF CLASSIFICATION (GAS) |
Zones 1 and 2, Gas groups IIA, IIB and IIC |
|||||
TEMPERATURE CLASS (GAS) |
T3 |
T3 |
||||
AREA OF CLASSIFICATION (DUST) |
Zones 21 and 22, Dust Groups IIIA, IIIB and IIIC |
|||||
MAX. SURFACE TEMPERATURE (DUST) |
T195°C |
T195°C |
||||
AMBIENT TEMPERATURE |
400VA -20°C to +35°C 320VA -20°C to +50°C |
400VA -20°C to +30°C 320VA -20°C to +42°C |
||||
CERTIFICATE |
ATEX - LCIE02ATEX6248X IECEX - LCI 04.0016X |
ATEX - LCIE02ATEX6118X IECEX - LCI 11.0008X |
||||
ENCLOSURE |
Glass reinforced polyester (GRP) enclosure, marine grade (316L) stainless steel skid |
Marine grade (316L) stainless steel enclosure and skid |
||||
POWER |
320 / 400VA |
320 / 400VA |
||||
VOLTS IN |
110V ac +6% - 10% |
230V ac +6% -10% |
110V ac +6% -10% |
230V ac +6% -10% |
||
INPUT CABLE |
15m SY cable 2.5mm² with ATX 110V / 230V 2P+E plug fitted as standard |
|||||
VOLTS OUT |
24V |
110V |
24V |
110V |
||
SOCKET ARRANGEMENT & CONFIGURATION |
4 output sockets, ATX 110V / 24V 2P+E as standard |
|||||
2 sockets on each unit side |
||||||
DIMENSIONS |
504 x 465 x 285mm (L x W x H) |
512 x 562 x 260 mm (L x W x H) |
||||
INGRESS PROTECTION |
IP66 |
|||||
WEIGHT |
21 kg |
28 kg |